Description
Heating controller LK 110 SmartComfort helps save:
- By measuring the heating water and outdoor temperatures, the LK 110 SmartComfort heating controller regulates the mixing valve so that exactly the required amount of heat is supplied to the system at any given time. The controller display allows you to view the heating water and outdoor temperatures at any time.
- The LK 110 SmartComfort heating controller has automatic direction selection to adapt to the opening direction of the mixing valve. LED indicators show whether the controller is opening or closing the valve. The heating water temperature can be limited by maximum and minimum values.
- Symbols on the controller indicate the selected function, and the LED display shows the function setting or value. Adjustment is simple using the “+” and “-” push buttons.
- Depending on the size of the heating system and the building’s thermal insulation, the heating curve slope may need to be adjusted to achieve the desired room temperature. The heating curve slope and parallel shift are easy to adjust using the push buttons.
- The LK 110 SmartComfort heating controller is easy to install on both new and existing valves. The plug-in power adapter enables quick and easy installation. In the event of a power failure, the controller retains its settings and the actuator stops. The mixing valve can be turned manually by disconnecting the actuator coupling.
Technical data for the LK 110 SmartComfort heating controller:
- Power adapter input voltage 100-240 VAC, 50/60 Hz
- Power adapter output voltage 24 VDC
- Power consumption < 3 VA
- Protection class: III SELV (EN 60730-1) (double insulation)
- Ambient temperature, actuator and room sensor: 0 – +50°C, Humidity: <90% Rh
- Protection class, actuator: IP 42 – upright, IP 40 – in other positions (according to EN 60529)
- Protection class, room sensor: IP 20 (according to EN 60529)
- Protection class, outdoor sensor: IP 66 (according to EN 60529)
- Protection class, power supply unit: IP 20 (according to EN 60529)
- Power supply connection: Euro plug CEE 7-6
- Actuator rotation angle / direction: 90° / clockwise and counterclockwise
- Actuator torque: 5 Nm
- Measuring range, outdoor temperature: -50°C – +50°C
- Heating water temperature setting range +5°C – 99°C
- Control curve: 1.0 – 9.9
- Parallel shift of control curve: ± 10°C
- Minimum heating water temperature +5°C – +40°C
- Maximum heating water temperature +20°C – +99°C
- Dimensions, actuator – length x width x height 93 x 80 x 75 mm
- Dimensions, room sensor – width x height x depth: 83 x 80 x 27 mm
- Dimensions, power supply unit – length x width x height: 74 x 30 x 43 mm
- Manufacturer: LK Armatur AB